Inspur New-generation Water Cooling Cabinet TS4280C

Water cooling cabinet TS4280C water-cooling system is mainly utilized in environments with various types of data center server racks and specially designed to address the high temperatures and density problem. The water cooling cabinet is cooled by chilled water and the water flows in/out from the bottom. The use of elevated flooring in the machine room or simple steel structures is recommended. Power cables are introduced on top. Heavy and light-current wires and cables may be isolated by fixed cable troughs on top of the cabinet. They will enter the equipment via the heavy and light-current wire holes respectively.

Functional Features

Functions and features:

Supercomputer has a massive volume (normally comprising hundreds of blade servers) and generates high amounts of heat. Therefore the operating environment of a supercomputer has to satisfy stringent requirements. The cabinet needs to be of high quality to satisfy load-bearing requirements while the heat emission requires the installation of a refrigerator that dissipates over 25kw for the single cabinet. Inspur new-generation water cooling cabinet TS4280C has a refrigerating capacity of 40KW, compared to the 20-30KW refrigerating capacity of the cabinets of most other manufacturers.

This cabinet is used for high-performance computing, image processing and other high-end and high-density data center application scenes to satisfy the refrigerating needs in many types of working conditions.

General descriptions

The cabinet is designed to be transparent with an elegant profile.

The cabinet is enclosed as a whole with internal air circulation and refrigeration; the single cabinet has a refrigerating capacity of 40KW;

6 hot-plug fans with a maximum air flow rate of 8,000m3/h;

Support local and remote monitoring and management.

Product Information

Water cooling cabinet TS4280 water cooling system (hereinafter referred to as the equipment) is mainly utilized in environments with various types of data center server racks specially designed to address the problems of high temperatures and densities. The water cooling cabinet is cooled by chilled water and the water flows in/out at the bottom. The use of elevated flooring in the machine room or simple steel structures is recommended. Power cables are introduced on top. Heavy and light-current wires and cables may be isolated by fixed cable troughs on top of the cabinet. They will enter the equipment via the heavy and light-current wire holes respectively.

Working principles

The equipment has an integrated enclosed structure to prevent forced convection between the inside and outside of the cabinet so as to achieve independent refrigerating circulation of the equipment to the minimum extent. In other words, Inspur water cooling cabinet equipment can be deemed to be independent from the machine room environment in terms of refrigerating effects. This equipment can work properly even when the machine room has a high temperature range. As the following figure shows, internal air flows between the IT data cabinet and the air-conditioner cabinet. The hot air streams heated by the IT server enter the air-conditioner cabinet via the ventilating meshes at the back, and the cooling water coil unit in the air-conditioner cabinet carries the heat away to cool the air flows. The cooled air then flows back into the front of the IT data cabinet via the ventilating meshes in the front of the cabinet, and finally feed into the IT server for heat radiation. When the IT server load reaches 40KW, the temperature of the hot air flow will normally approach 50. After the highly efficient cooling, the temperature of the low-temperature air flows can be contained within 26.

Performance features:

Highly efficient deployment

Structurally, the water cooling cabinet TS4280C comprises air-conditioner cabinet and IT data cabinet. Both cabinets can be dismantled and assembled.

Such design and deployment represent an integrated structural design and once-off seamless installation and eliminate the trouble of cabinet connection. The structure is also more stable.

High refrigerating capacity and high density

Water cooling cabinet TS4280C has a refrigerating capacity over 40KW.

It supports an IT cabinet heating density of 1KW/U.

A professional solution for blade server and other high-density servers.

Power supply solution

TS4280C water cooling cabinet supports dual-circuit AC inputs and is highly safe and stable;

It provides two IT data cabinet configuration plans to adapt to different customer needs;

When the total power demand is lower than 30KW, a single 40-port universal plug PDU is adopted;

When the total power demand is over 30KW, two PDUs are adopted (single 27-port universal plug)

Three-layer condensate water protection plan

Inspur TS4280C water cooling cabinet has a unique three-layer condensate water protection plan. First layer: condensation discharged from the water pan through deadweight; second layer: low-level water soaking actuation to launch the condensate water discharge pump; third layer: high-level water soaking actuation to activate full pan alarm and urge manual on-site handling. The refrigerating system's safe and efficient operation is guaranteed by the three layers of protection.

Mute design

Inspur TS4280C water cooling cabinet has one unique set of mute design.

It has 5+1 fan redundancy; hot-plug fan design; more than 80% ventilation mesh design

As such, the total cabinet noise level does not exceed 75DB, which sets the pace for domestic standards.

Unparalleled reliability

Inspur TS4280C water cooling cabinet is designed to have 5 million door opening cycles and an opening/closing frequency of 3,000 cycles per hour in order to satisfy the needs of different customers and to increase the reliability of the cabinet. A breakwater is provided to prevent condensation from entering the IT data cabinet. EC turbo fan with 5+1 redundant design is adopted; water cooling module and dual-circuit external power supplies are supported to ensure reliable refrigeration. Forced drainage of condensation and a three-layered condensation protection plan are further provided.

Three temperature sensors are installed to accurately monitor the air feeding and return temperatures.

Multifunctional interactive interface

Inspur TS4280C water cooling cabinet is furnished with the multifunctional interactive interface system independently designed and developed by Inspur. It provides interactive menus and enables password protection, flash screen alarm and supports remote monitoring. 

Technical Specifications

1.NameTS4280C  

Transparent design with an elegant profile.

40KW Enclosed cabinet structure and internal air circulation and refrigeration with a unit refrigerating capacity of 40KW;

6 hot-plug fans with a maximum flow rate of 8,000m3/h;

Supports local and remote monitoring and management mode.

2.General descriptions

This cabinet is used for high-performance computing, graph processing and other high-end and high-density data center application scenes and can satisfy the refrigerating needs in various working conditions.

3.Detailed parameters 

General dimensions

900mm (W) x1400mm (D) x2000mm (H)

Data cabinet dimensions

600mm (W) x1400mm (D) x2000mm (H)

Air conditioner cabinet dimensions

300mm (W) x1400mm (D) x2000mm (H)

Refrigerating capacity

40KW

Data cabinet space

42U, 19inch standard cabinet width

Max. air flow

8000m3/h

Rated power

2.8KW

Working voltage

Data cabinet—AC3P 380V 50/60HZ

Air-conditioner cabinet—AC1P 220V 50/60HZ (dual-circuit power supplies permitted)

Static loading capacity

1000KG

Working environmental temperature

645

Working environmental humidity

5%85% R.H.

Noise

75dB  (1m sound pressure)

I/O pipe gauge

DN401” 1/2

Working water pressure

16Bar at the maximum

PDU

Dual PDU support

27-port GB universal socket

Monitoring

Support IPMI protocol; support open RJ45 and RS485 protocol

Communication interface supports Ethernet and Modbus

User Manual

 